CIP Safety

Быстрая, простая и гибкая интеграция безопасности в производственные линии.

Спецификации и заказ

Unit typeAppearanceSupported communications protocolNumber of communications connectorsNetwork variablesUnit versionOrder code
Communication Control UnitEtherNet/IP 2 Routing of the CIP Safety protocol is supported.32 2 PORT1 is an independent port. PORT2A and PORT2B are the ports with a built-in Ethernet switch.Ver. 1.01NX-CSG320
Unit typeAppearanceSpecificationsUnit versionOrder codeMaximum number of safety I/O pointsProgram capacityNumber of safety I/O connectionsI/O refreshing method
Safety CPU Unit (NX-SL5 ??? )1024 points2048 KB128Free-Run refreshingVer. 1.3NX-SL5500
2032 points4096 KB254NX-SL5700
Unit typeAppearanceSpecificationsUnit versionOrder codeNumber of safety input pointsNumber of test output pointsInternal I/O commonRated input voltageOMRON special safety input devicesNumber of safety slave connectionsI/O refreshing method
Safety Input Units4 points2 pointsSinking inputs (PNP)24 VDCCannot be connected. 2 Various OMRON special safety input devices can be connected directly without a special controller. For detail of connectable OMRON special safety input devices, refer to NX-series User's Manual Safety Control Unit/Communication Control Unit (Cat. No. Z395).1Free-Run refreshingVer. 1.1NX-SIH400
8 pointsCannot be connected.Ver. 1.0NX-SID800
Unit typeAppearanceSpecificationsUnit versionOrder codeNumber of safety output pointsInternal I/O commonMaximum load currentRated voltageNumber of safety slave connectionsI/O refreshing method
Safety Output Units2 pointsSourcing outputs (PNP)2.0 A/point, 4.0 A/Unit at 40°C, and 2.5 A/Unit at 55°C The maximum load current depends on the installation orientation and ambient temperature.24 VDC1Free-Run refreshingVer. 1.0NX-SOH200
4 points0.5 A/point and 2.0 A/UnitNX-SOD400
Product nameSpecificationsNumber of licensesMediaOrder code
Sysmac Studio Safety Edition Ver. 1. ?? 2 The Safety Edition can be used with the Communication Control Unit and EtherNet/IP Coupler Unit.Sysmac Studio Safety Edition is a license including necessary setting functions for the safety control system. Note:This product is a license only. You need the Sysmac Studio Standard Edition DVD media to install it.1 license-SYSMAC-FE001L
Sysmac Studio Standard Edition Ver. 1. ?? 2 The Sysmac Studio Standard Edition License (SYSMAC-SE2 ?? L) includes functions that the Safety Edition (SYSMAC-FE001L) provides. The Communication Control Unit can be used with the Sysmac Studio version 1.24 or higher.The Sysmac Studio is the software that provides an integrated environment for setting, programming, debugging and maintenance of machine automation controllers including the NJ/NX-series CPU Units, NY-series Industrial PC, EtherCAT Slave, and the HMI. Sysmac Studio runs on the following OS. Windows 7(32-bit/64-bit version)/8(32-bit/64-bit version)/8.1(32-bit/64-bit version)/10(32-bit/64-bit version)- (Media only)DVDSYSMAC-SE200D
Product nameSpecificationsOrder code
Memory CardSD memory card, 2 GBHMC-SD291
SD memory card, 4 GBHMC-SD491
Unit/Terminal Block Coding PinsFor 10 Units (Terminal Block: 30 pins, Unit: 30 pins)NX-AUX02
Product nameSpecificationsOrder codeNo. of terminalsTerminal number indicationsGround terminal markTerminal current capacity
Terminal Block8A/BProvided10 ANX-TBC082
8A/BNone10 ANX-TBA082
16A/BNone10 ANX-TBA162
Product nameRemarkOrder code
End CoverOne End Cover is provided with the Communication Control Unit.NX-END02

Модуль коммуникационного шлюза серии NX

Unit typeAppearanceSupported communications protocolNumber of communications connectorsNetwork variablesUnit versionOrder code
Communication Control UnitEtherNet/IP 2 Routing of the CIP Safety protocol is supported.32 2 PORT1 is an independent port. PORT2A and PORT2B are the ports with a built-in Ethernet switch.Ver. 1.01NX-CSG320

Блоки управления безопасностью серии NX

Unit typeAppearanceSpecificationsUnit versionOrder codeMaximum number of safety I/O pointsProgram capacityNumber of safety I/O connectionsI/O refreshing method
Safety CPU Unit (NX-SL5 ??? )1024 points2048 KB128Free-Run refreshingVer. 1.3NX-SL5500
2032 points4096 KB254NX-SL5700
Unit typeAppearanceSpecificationsUnit versionOrder codeNumber of safety input pointsNumber of test output pointsInternal I/O commonRated input voltageOMRON special safety input devicesNumber of safety slave connectionsI/O refreshing method
Safety Input Units4 points2 pointsSinking inputs (PNP)24 VDCCannot be connected. 2 Various OMRON special safety input devices can be connected directly without a special controller. For detail of connectable OMRON special safety input devices, refer to NX-series User's Manual Safety Control Unit/Communication Control Unit (Cat. No. Z395).1Free-Run refreshingVer. 1.1NX-SIH400
8 pointsCannot be connected.Ver. 1.0NX-SID800
Unit typeAppearanceSpecificationsUnit versionOrder codeNumber of safety output pointsInternal I/O commonMaximum load currentRated voltageNumber of safety slave connectionsI/O refreshing method
Safety Output Units2 pointsSourcing outputs (PNP)2.0 A/point, 4.0 A/Unit at 40°C, and 2.5 A/Unit at 55°C The maximum load current depends on the installation orientation and ambient temperature.24 VDC1Free-Run refreshingVer. 1.0NX-SOH200
4 points0.5 A/point and 2.0 A/UnitNX-SOD400

Модули ЦПУ безопасности

Unit typeAppearanceSpecificationsUnit versionOrder codeMaximum number of safety I/O pointsProgram capacityNumber of safety I/O connectionsI/O refreshing method
Safety CPU Unit (NX-SL5 ??? )1024 points2048 KB128Free-Run refreshingVer. 1.3NX-SL5500
2032 points4096 KB254NX-SL5700

Блоки безопасного входа

Unit typeAppearanceSpecificationsUnit versionOrder codeNumber of safety input pointsNumber of test output pointsInternal I/O commonRated input voltageOMRON special safety input devicesNumber of safety slave connectionsI/O refreshing method
Safety Input Units4 points2 pointsSinking inputs (PNP)24 VDCCannot be connected. 2 Various OMRON special safety input devices can be connected directly without a special controller. For detail of connectable OMRON special safety input devices, refer to NX-series User's Manual Safety Control Unit/Communication Control Unit (Cat. No. Z395).1Free-Run refreshingVer. 1.1NX-SIH400
8 pointsCannot be connected.Ver. 1.0NX-SID800

Блоки безопасного вывода

Unit typeAppearanceSpecificationsUnit versionOrder codeNumber of safety output pointsInternal I/O commonMaximum load currentRated voltageNumber of safety slave connectionsI/O refreshing method
Safety Output Units2 pointsSourcing outputs (PNP)2.0 A/point, 4.0 A/Unit at 40°C, and 2.5 A/Unit at 55°C The maximum load current depends on the installation orientation and ambient temperature.24 VDC1Free-Run refreshingVer. 1.0NX-SOH200
4 points0.5 A/point and 2.0 A/UnitNX-SOD400

Программное обеспечение для автоматизации Sysmac Studio

Пожалуйста, приобретите DVD и необходимое количество лицензий при первой покупке Sysmac Studio. DVD-диски и лицензии доступны индивидуально. Каждая модель лицензий не включает DVD.

Product nameSpecificationsNumber of licensesMediaOrder code
Sysmac Studio Safety Edition Ver. 1. ?? 2 The Safety Edition can be used with the Communication Control Unit and EtherNet/IP Coupler Unit.Sysmac Studio Safety Edition is a license including necessary setting functions for the safety control system. Note:This product is a license only. You need the Sysmac Studio Standard Edition DVD media to install it.1 license-SYSMAC-FE001L
Sysmac Studio Standard Edition Ver. 1. ?? 2 The Sysmac Studio Standard Edition License (SYSMAC-SE2 ?? L) includes functions that the Safety Edition (SYSMAC-FE001L) provides. The Communication Control Unit can be used with the Sysmac Studio version 1.24 or higher.The Sysmac Studio is the software that provides an integrated environment for setting, programming, debugging and maintenance of machine automation controllers including the NJ/NX-series CPU Units, NY-series Industrial PC, EtherCAT Slave, and the HMI. Sysmac Studio runs on the following OS. Windows 7(32-bit/64-bit version)/8(32-bit/64-bit version)/8.1(32-bit/64-bit version)/10(32-bit/64-bit version)- (Media only)DVDSYSMAC-SE200D

Дополнительные продукты

Product nameSpecificationsOrder code
Memory CardSD memory card, 2 GBHMC-SD291
SD memory card, 4 GBHMC-SD491
Unit/Terminal Block Coding PinsFor 10 Units (Terminal Block: 30 pins, Unit: 30 pins)NX-AUX02
Product nameSpecificationsOrder codeNo. of terminalsTerminal number indicationsGround terminal markTerminal current capacity
Terminal Block8A/BProvided10 ANX-TBC082
8A/BNone10 ANX-TBA082
16A/BNone10 ANX-TBA162
Product nameRemarkOrder code
End CoverOne End Cover is provided with the Communication Control Unit.NX-END02

Аксессуары для блока управления связью

Product nameRemarkOrder code
End CoverOne End Cover is provided with the Communication Control Unit.NX-END02
Certification bodyStandards
T?V Rheinland 2 The FSoE protocol was certified for applications in which OMRON FSoE devices are connected to each other. For compatibility with FSoE devices other than OMRON FSoE devices, the customer must validate FSoE communications.EN ISO 13849-1EN ISO 13849-2IEC 61508 parts 1-7IEC/EN 62061IEC/EN 61131-2
ULNRAQ (UL61010-1, and UL 61010-2-201)NRAG (ANSI/ISA 12.12.01, or UL 121201)NRAQ7 (CSA C22.2 No. 61010-1, and CSA C22.2 No. 61010-2-201)FSPC (IEC 61508 and ISO 13849) 2 Only NX-SL5500/5700 have obtained IEC 61131-6 and FSPC certifications.
Certification bodyStandards
ULNRAQ (UL61010-1, and UL 61010-2-201)NRAG (UL 121201)
ItemSpecifications
EnclosureMounted in a panel (open)
Grounding methodGround to 100 ? or less
Operating environmentAmbient operating temperature
Ambient operating humidity10% to 95% (with no condensation or icing)
AtmosphereMust be free from corrosive gases.
Ambient storage temperature?25 to 70°C (with no condensation or icing)
Altitude2,000 m max.
Pollution degree2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise immunityConforms to IEC 61131-2. 2 kV on power supply line
Insulation classClass III (SELV)
Overvoltage categoryCategory II: Conforms to JIS B3502 and IEC 61131-2.
EMC immunity levelZone B
Vibration resistanceConforms to IEC 60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude 8.4 to 150 Hz, acceleration of 9.8 m/s 2 100 minutes each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
Shock resistanceConforms to IEC 60068-2-27. 147 m/s 2 , 3 times each in X, Y, and Z directions
Insulation resistance 2 The specifications are for the Communication Control Unit, Safety Input Unit, and Safety Output Unit, not for the Safety CPU Unit.20 M? between isolated circuits (at 100 VDC)
Dielectric strength 2 The specifications are for the Communication Control Unit, Safety Input Unit, and Safety Output Unit, not for the Safety CPU Unit.510 VAC for 1 min between isolated circuits, leakage current: 5 mA max.
Installation methodDIN Track (IEC 60715 TH35-7.5/TH35-15)
Col1Col2
Unit nameCommunication Control Unit
ModelNX-CSG320
Indicators
Hardware switch settings
Dimensions 2 Includes the End Cover, and does not include projecting parts.72 x 100 x 90 mm (W x H x D)
Weight 2 Includes the End Cover. The weight of the End Cover is 82 g.390 g
Number of NX Units that you can connect32 units or less
Number of communications that can be set between NX Units254 ports max. 2 Includes the SD Memory Card. The NX Unit power consumption to NX Units is not included.
Unit power supplyPower supply voltage
Unit power consumption 2 This is the inrush current value when the power supply turns ON after it has been OFF. The inrush current may vary depending on the operating condition and other conditions. Therefore, select fuses, breakers, and external power supply devices that have enough margin in characteristic and capacity, considering the condition under which the devices are used. Especially when you turn the power ON/OFF through a switch inserted to the external DC power supply, cycling power ON-OFF-ON within one second will cause the inrush current of approx. 30 A/0.3 mA to occur since the inrush current limiter circuit fails to limit the current.5.95 W
Inrush current 2 The amount of current that can be passed constantly through the terminal. Do no exceed this current value when you use a through-wiring for the Unit power supply.For cold start at room temperature: 10 A max./0.1 ms max. and 2.5 A max./150 ms max.
Current capacity of power supply terminal 2 The actual configurable number can be calculated as follows: 254 - <Number of CIP Safety connections configured> - <Number of FSoE connections configured>4 A
Isolation methodNo isolation: Between the Unit power supply terminal and internal circuit
Power supply to the NX Unit power supplyNX Unit power supply capacity
NX Unit power supply efficiency80%
Isolation methodNo isolation: Between the Unit power supply terminal and NX Unit power supply
I/O power supply to NX UnitsPower supply voltage
Maximum I/O power supply current4 A
Current consumption from I/O power supply10 mA max. (24 VDC)
External connection terminalsScrewless clamping terminal block (8 terminals)
Terminal connection diagram
AccessoriesEnd cover (NX-END02): 1 pc.
Installation orientation and restrictionsOnly upright installation orientation
ItemSpecificationsNX-CSG- ???
Communications protocolTCP/IP or UDP/IP
Supported servicesSysmac Studio connection, tag data links, CIP message communications, FTP server, automatic clock adjustment (NTP client), SNMP (agent), DNS (client), BOOTP (client), TCP/UDP message service
Number of logical ports2 (With IP routing function)
Physical layer100Base-TX or 10Base-T (100Base-TX is recommended.) 2 If tag data links are being used, use 100Base-TX.
Transmission specificationsMedia access methodCSMA/CD
ModulationBaseband
Transmission pathsStar form
Baud rate100 Mbps (100BASE-TX)
Transmission mediaShielded twisted-pair (STP) cable, Category 5, 5e or higher
Transmission distance100 m max. (distance between hub and node)
Number of cascade connectionsThe built-in switching ports support up to 50 nodes. There is no limitation when an external Ethernet switch is used.
CIP Safety routingMaximum number of routable CIP Safety connections254 total For multi-cast connections, 128 total
Maximum routable Safety data length per connection32 bytes
CIP service: Tag data links (cyclic communications)Number of connections32/Logical ports (total of 64 with two logical ports)
Packet interval (refresh cycle)1 to 10,000 ms in 1-ms increments
Packet intervals can be set independently for each connection. (Data is refreshed over the network at preset intervals and does not depend on the number of nodes.)
Allowed communications bandwidth per Unit12,000 pps 2 Here, pps means "packets per second" and indicates the number of packets that can be processed in one second. Note:The heartbeat and CIP Safety routing are included.
Number of registrable tags1024/Logical ports (total of 2048 with two logical ports)
Tag typesNetwork variables
Number of tags per connection (=1 tag set)32 (31 tags if Controller status is included in the tag set.)
Maximum link data size per node46,208 bytes/Logical ports 92,416 bytes total
Maximum data size per connection1,444 bytes 2 To use a data size of 505 bytes or higher, the system must support a large forward open (an optional CIP specification). The CS, CJ, NJ, and NX-series Units support a large forward open, but before connecting to nodes of other companies, confirm that those devices also support it.
Number of registrable tag setsData concurrency is maintained within each connection.
32 per port (1 connection = 1 tag set) (total of 40 with two logical ports) 2 If more than 40 tag sets are registered in total, the Tag Data Link, Too Many Tag Sets Registered (840E0000 hex) event will occur.
Maximum size of 1 tag set1,444 bytes (Two bytes are used if Controller status is included in the tag set.)
Multi-cast packet filter 2 Because the built-in EtherNet/IP port is equipped with an IGMP client (version 2), unnecessary multicast packets can be filtered out by an Ethernet switch that supports IGMP Snooping.Supported.
CIP message service: Explicit messages 2 The built-in EtherNet/IP port uses the TCP/UDP port numbers shown in the following table. Do not set the same port number for more than one TCP/UDP service.Class 3 (number of connections)Connections: 16/Logical ports (total of 32 with two logical ports) (server only)
UCMM (unconnected)Maximum number of clients that can communicate at one time: 16 per port (total of 32 with two logical ports)Maximum number of servers that can communicate at one time: 16 per port (total of 32 with two logical ports)
TCP/UDP message serviceMaximum number of clients that can communicate at one time16 per port (total of 32 with two logical ports)
Maximum message sizeRequest: 492 bytes Response: 496 bytes
SNMPAgentSNMPv1, SNMPv2c
MIBMIB-II
EtherNet/IP conformance testConforms to CT14
Ethernet interface10BASE-T or 100BASE-TX Auto negotiation or fixed settings
ServiceTypePort numberRemarks
Tag data linksUDP2222Fixed values
Used by systemUDP2223, 2224
TCP9610
CIP messagesTCP44818
FTP client (Data transfer port)TCP20
DNS clientTCP/UDP53
BOOTP clientUDP68
HTTP serverTCP80
Used by system, otherTCP/UDP9600You can change the port number in the Unit Settings on the Sysmac Studio.
FTP client (Control port)TCP21
TCP/UDP message serviceTCP/UDP64000
NTP clientUDP123
SNMP agentUDP161
SNMP trapUDP162
Unit nameSafety CPU Unit
ModelNX-SL5500
Maximum number of safety I/O points1024 points
Program capacity2048 KB
Number of safety master connections 2 This is the maximum number of Safety I/O connections that can be set to this Unit. The value is the total number of CIP Safety originator connections, CIP Safety target connections, and FSoE master connections.128
Number of CIP Safety originator connections128
Number of CIP Safety target connections4
Number of originators that can be connected with a multi-cast connection8
Number of FSoE master connections128
I/O refreshing methodFree-Run refreshing
External connection terminalsNone
Indicators
Hardware switch settings
Dimensions30 x 100 x 71 mm (W x H x D)
I/O power supply methodNot supplied.
Current capacity of I/O power supply terminalsNo I/O power supply terminals
NX Unit power consumption3.35 W max. 2 The cable length for the Units (Communication Control Unit and Power Supply Unit for NX Units) that supply power to the corresponding Unit must be up to 20 m.
Current consumption from I/O power supplyNo consumption
Weight130 g max.
Installation orientation and restrictionsInstallation orientation: Upright installation Restriction 2 Only NX102 CPU Units and Communication Control Units can be connected. NX1P2 CPU Units or Communications Coupler Units cannot be connected. : None.
Unit nameSafety Input Unit
ModelNX-SIH400
Number of safety input points4 points
Number of test output points2 points
Internal I/O commonPNP (sinking inputs)
Rated input voltage24 VDC (20.4 to 28.8 VDC)
OMRON special safety input devicesCan be connected.
Number of safety slave connections1
I/O refreshing methodFree-Run refreshing
External connection terminalsScrewless clamping terminal block (8 terminals)
Indicators
Safety input current4.5 mA TYP.
Safety input ON voltage11 VDC min.
Safety input OFF voltage/OFF current5 VDC max., 1 mA max.
Test output typeSourcing outputs (PNP)
Test output load current25 mA max.
Test output residual voltage1.2 V max. (Between IOV and all output terminals)
Test output leakage current0.1 mA max.
Dimensions12 x 100 x 71 mm (W x H x D)
Isolation methodPhotocoupler isolation
Insulation resistance20 MOhm min. between isolated circuits (at 100 VDC)
Dielectric strength510 VAC for 1 min between isolated circuits, leakage current: 5 mA max.
I/O power supply methodPower supplied from the NX bus
Current capacity of I/O power supply terminalsNo applicable terminals.
NX Unit power consumptionConnected to a CPU Unit or a Communication Control Unit 1.10 W max.Connected to a Communications Coupler Unit 0.70 W max.
Current consumption from I/O power supply20 mA max.
Weight70 g max.
Circuit layout
Terminal connection diagram
Installation orientation and restrictionsInstallation orientation: Connected to a CPU Unit or a Communication Control Unit 2 Only NX102 CPU Units and Communication Control Units can be connected. NX1P2 CPU Units cannot be connected. Possible in the upright installation orientation. Connected to a Communications Coupler Unit 6 possible orientations. Restrictions: Maximum ambient temperature is 50°C for any orientation other than upright installation.
Protective functionsOvervoltage protection circuit and short detection (test outputs)
Unit nameSafety Output UnitModelNX- SOH200NX- SOD400
Number of safety output points2 points4 points
Internal I/O commonPNP (sourcing outputs)
Maximum load current2.0 A/point 4.0 A/Unit at 40°C 2.5 A/Unit at 55°CThe maximum load current depends on the installation orientation and ambient temperature0.5 A/point and 2.0 A/Unit
Rated voltage24 VDC (20.4 to 28.8 VDC)
Number of safety slave connections1
I/O refreshing methodFree-Run refreshing
External connection terminalsScrewless clamping terminal block (8 terminals)
Indicators
Safety output ON residual voltage1.2 V max. (Between IOV and all output terminals)
Safety output OFF residual voltage2 V max. (Between IOG and all output terminals)
Safety output leakage current0.1 mA max.
Dimensions12 x 100 x 71 mm (W x H x D)
Isolation methodPhotocoupler isolation
Insulation resistance20 MOhm min. between isolated circuits (at 100 VDC)
Dielectric strength510 VAC for 1 min between isolated circuits, leakage current: 5 mA max.
I/O power supply methodPower supplied from the NX bus
Current capacity of I/O power supply terminalsIOG: 2 A max./terminalIOG (A3 and B3): 2 A max./terminal IOG (A7 and B7): 0.5 A max./terminal
NX Unit power consumptionConnected to a CPU Unit or a Communication Control Unit 1.05 W max. Connected to a Communications Coupler Unit 0.70 W max.Connected to a CPU Unit or a Communication Control Unit 1.10 W max. Connected to a Communications Coupler Unit 0.75 W max.
Current consumption from I/O power supply40 mA max.60 mA max.
Weight65 g max.
Circuit layout
Terminal connection diagram
Installation orientation and restrictionsInstallation orientation: Connected to a CPU Unit or a Communication Control Unit 2 Only NX102 CPU Units and Communication Control Units can be connected. NX1P2 CPU Units cannot be connected. Possible in the upright installation orientation. Connected to a Communications Coupler Unit 6 possible orientations. Restrictions: None
Protective functionsOvervoltage protection circuit and short detection (test outputs)

Правила и стандарты

Certification bodyStandards
T?V Rheinland 2 The FSoE protocol was certified for applications in which OMRON FSoE devices are connected to each other. For compatibility with FSoE devices other than OMRON FSoE devices, the customer must validate FSoE communications.EN ISO 13849-1EN ISO 13849-2IEC 61508 parts 1-7IEC/EN 62061IEC/EN 61131-2
ULNRAQ (UL61010-1, and UL 61010-2-201)NRAG (ANSI/ISA 12.12.01, or UL 121201)NRAQ7 (CSA C22.2 No. 61010-1, and CSA C22.2 No. 61010-2-201)FSPC (IEC 61508 and ISO 13849) 2 Only NX-SL5500/5700 have obtained IEC 61131-6 and FSPC certifications.
Certification bodyStandards
ULNRAQ (UL61010-1, and UL 61010-2-201)NRAG (UL 121201)

Блоки управления безопасностью серии NX

Блоки управления безопасностью серии NX также зарегистрированы на соответствие требованиям RCM, EAC и KC.

Certification bodyStandards
T?V Rheinland 2 The FSoE protocol was certified for applications in which OMRON FSoE devices are connected to each other. For compatibility with FSoE devices other than OMRON FSoE devices, the customer must validate FSoE communications.EN ISO 13849-1EN ISO 13849-2IEC 61508 parts 1-7IEC/EN 62061IEC/EN 61131-2
ULNRAQ (UL61010-1, and UL 61010-2-201)NRAG (ANSI/ISA 12.12.01, or UL 121201)NRAQ7 (CSA C22.2 No. 61010-1, and CSA C22.2 No. 61010-2-201)FSPC (IEC 61508 and ISO 13849) 2 Only NX-SL5500/5700 have obtained IEC 61131-6 and FSPC certifications.

Блок управления связью серии NX

Блоки управления связью серии NX также зарегистрированы в соответствии с требованиями RCM, EAC и KC.

Certification bodyStandards
ULNRAQ (UL61010-1, and UL 61010-2-201)NRAG (UL 121201)

Общие характеристики

ItemSpecifications
EnclosureMounted in a panel (open)
Grounding methodGround to 100 ? or less
Operating environmentAmbient operating temperature
Ambient operating humidity10% to 95% (with no condensation or icing)
AtmosphereMust be free from corrosive gases.
Ambient storage temperature?25 to 70°C (with no condensation or icing)
Altitude2,000 m max.
Pollution degree2 or less: Conforms to JIS B3502 and IEC 61131-2.
Noise immunityConforms to IEC 61131-2. 2 kV on power supply line
Insulation classClass III (SELV)
Overvoltage categoryCategory II: Conforms to JIS B3502 and IEC 61131-2.
EMC immunity levelZone B
Vibration resistanceConforms to IEC 60068-2-6. 5 to 8.4 Hz with 3.5-mm amplitude 8.4 to 150 Hz, acceleration of 9.8 m/s 2 100 minutes each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
Shock resistanceConforms to IEC 60068-2-27. 147 m/s 2 , 3 times each in X, Y, and Z directions
Insulation resistance 2 The specifications are for the Communication Control Unit, Safety Input Unit, and Safety Output Unit, not for the Safety CPU Unit.20 M? between isolated circuits (at 100 VDC)
Dielectric strength 2 The specifications are for the Communication Control Unit, Safety Input Unit, and Safety Output Unit, not for the Safety CPU Unit.510 VAC for 1 min between isolated circuits, leakage current: 5 mA max.
Installation methodDIN Track (IEC 60715 TH35-7.5/TH35-15)

Блок управления связью

Col1Col2
Unit nameCommunication Control Unit
ModelNX-CSG320
Indicators
Hardware switch settings
Dimensions 2 Includes the End Cover, and does not include projecting parts.72 x 100 x 90 mm (W x H x D)
Weight 2 Includes the End Cover. The weight of the End Cover is 82 g.390 g
Number of NX Units that you can connect32 units or less
Number of communications that can be set between NX Units254 ports max. 2 Includes the SD Memory Card. The NX Unit power consumption to NX Units is not included.
Unit power supplyPower supply voltage
Unit power consumption 2 This is the inrush current value when the power supply turns ON after it has been OFF. The inrush current may vary depending on the operating condition and other conditions. Therefore, select fuses, breakers, and external power supply devices that have enough margin in characteristic and capacity, considering the condition under which the devices are used. Especially when you turn the power ON/OFF through a switch inserted to the external DC power supply, cycling power ON-OFF-ON within one second will cause the inrush current of approx. 30 A/0.3 mA to occur since the inrush current limiter circuit fails to limit the current.5.95 W
Inrush current 2 The amount of current that can be passed constantly through the terminal. Do no exceed this current value when you use a through-wiring for the Unit power supply.For cold start at room temperature: 10 A max./0.1 ms max. and 2.5 A max./150 ms max.
Current capacity of power supply terminal 2 The actual configurable number can be calculated as follows: 254 - <Number of CIP Safety connections configured> - <Number of FSoE connections configured>4 A
Isolation methodNo isolation: Between the Unit power supply terminal and internal circuit
Power supply to the NX Unit power supplyNX Unit power supply capacity
NX Unit power supply efficiency80%
Isolation methodNo isolation: Between the Unit power supply terminal and NX Unit power supply
I/O power supply to NX UnitsPower supply voltage
Maximum I/O power supply current4 A
Current consumption from I/O power supply10 mA max. (24 VDC)
External connection terminalsScrewless clamping terminal block (8 terminals)
Terminal connection diagram
AccessoriesEnd cover (NX-END02): 1 pc.
Installation orientation and restrictionsOnly upright installation orientation
ItemSpecificationsNX-CSG- ???
Communications protocolTCP/IP or UDP/IP
Supported servicesSysmac Studio connection, tag data links, CIP message communications, FTP server, automatic clock adjustment (NTP client), SNMP (agent), DNS (client), BOOTP (client), TCP/UDP message service
Number of logical ports2 (With IP routing function)
Physical layer100Base-TX or 10Base-T (100Base-TX is recommended.) 2 If tag data links are being used, use 100Base-TX.
Transmission specificationsMedia access methodCSMA/CD
ModulationBaseband
Transmission pathsStar form
Baud rate100 Mbps (100BASE-TX)
Transmission mediaShielded twisted-pair (STP) cable, Category 5, 5e or higher
Transmission distance100 m max. (distance between hub and node)
Number of cascade connectionsThe built-in switching ports support up to 50 nodes. There is no limitation when an external Ethernet switch is used.
CIP Safety routingMaximum number of routable CIP Safety connections254 total For multi-cast connections, 128 total
Maximum routable Safety data length per connection32 bytes
CIP service: Tag data links (cyclic communications)Number of connections32/Logical ports (total of 64 with two logical ports)
Packet interval (refresh cycle)1 to 10,000 ms in 1-ms increments
Packet intervals can be set independently for each connection. (Data is refreshed over the network at preset intervals and does not depend on the number of nodes.)
Allowed communications bandwidth per Unit12,000 pps 2 Here, pps means "packets per second" and indicates the number of packets that can be processed in one second. Note:The heartbeat and CIP Safety routing are included.
Number of registrable tags1024/Logical ports (total of 2048 with two logical ports)
Tag typesNetwork variables
Number of tags per connection (=1 tag set)32 (31 tags if Controller status is included in the tag set.)
Maximum link data size per node46,208 bytes/Logical ports 92,416 bytes total
Maximum data size per connection1,444 bytes 2 To use a data size of 505 bytes or higher, the system must support a large forward open (an optional CIP specification). The CS, CJ, NJ, and NX-series Units support a large forward open, but before connecting to nodes of other companies, confirm that those devices also support it.
Number of registrable tag setsData concurrency is maintained within each connection.
32 per port (1 connection = 1 tag set) (total of 40 with two logical ports) 2 If more than 40 tag sets are registered in total, the Tag Data Link, Too Many Tag Sets Registered (840E0000 hex) event will occur.
Maximum size of 1 tag set1,444 bytes (Two bytes are used if Controller status is included in the tag set.)
Multi-cast packet filter 2 Because the built-in EtherNet/IP port is equipped with an IGMP client (version 2), unnecessary multicast packets can be filtered out by an Ethernet switch that supports IGMP Snooping.Supported.
CIP message service: Explicit messages 2 The built-in EtherNet/IP port uses the TCP/UDP port numbers shown in the following table. Do not set the same port number for more than one TCP/UDP service.Class 3 (number of connections)Connections: 16/Logical ports (total of 32 with two logical ports) (server only)
UCMM (unconnected)Maximum number of clients that can communicate at one time: 16 per port (total of 32 with two logical ports)Maximum number of servers that can communicate at one time: 16 per port (total of 32 with two logical ports)
TCP/UDP message serviceMaximum number of clients that can communicate at one time16 per port (total of 32 with two logical ports)
Maximum message sizeRequest: 492 bytes Response: 496 bytes
SNMPAgentSNMPv1, SNMPv2c
MIBMIB-II
EtherNet/IP conformance testConforms to CT14
Ethernet interface10BASE-T or 100BASE-TX Auto negotiation or fixed settings
ServiceTypePort numberRemarks
Tag data linksUDP2222Fixed values
Used by systemUDP2223, 2224
TCP9610
CIP messagesTCP44818
FTP client (Data transfer port)TCP20
DNS clientTCP/UDP53
BOOTP clientUDP68
HTTP serverTCP80
Used by system, otherTCP/UDP9600You can change the port number in the Unit Settings on the Sysmac Studio.
FTP client (Control port)TCP21
TCP/UDP message serviceTCP/UDP64000
NTP clientUDP123
SNMP agentUDP161
SNMP trapUDP162

Характеристики встроенного порта EtherNet/IP

В следующей таблице показаны характеристики встроенного порта EtherNet/IP модуля управления связью.

ItemSpecificationsNX-CSG- ???
Communications protocolTCP/IP or UDP/IP
Supported servicesSysmac Studio connection, tag data links, CIP message communications, FTP server, automatic clock adjustment (NTP client), SNMP (agent), DNS (client), BOOTP (client), TCP/UDP message service
Number of logical ports2 (With IP routing function)
Physical layer100Base-TX or 10Base-T (100Base-TX is recommended.) 2 If tag data links are being used, use 100Base-TX.
Transmission specificationsMedia access methodCSMA/CD
ModulationBaseband
Transmission pathsStar form
Baud rate100 Mbps (100BASE-TX)
Transmission mediaShielded twisted-pair (STP) cable, Category 5, 5e or higher
Transmission distance100 m max. (distance between hub and node)
Number of cascade connectionsThe built-in switching ports support up to 50 nodes. There is no limitation when an external Ethernet switch is used.
CIP Safety routingMaximum number of routable CIP Safety connections254 total For multi-cast connections, 128 total
Maximum routable Safety data length per connection32 bytes
CIP service: Tag data links (cyclic communications)Number of connections32/Logical ports (total of 64 with two logical ports)
Packet interval (refresh cycle)1 to 10,000 ms in 1-ms increments
Packet intervals can be set independently for each connection. (Data is refreshed over the network at preset intervals and does not depend on the number of nodes.)
Allowed communications bandwidth per Unit12,000 pps 2 Here, pps means "packets per second" and indicates the number of packets that can be processed in one second. Note:The heartbeat and CIP Safety routing are included.
Number of registrable tags1024/Logical ports (total of 2048 with two logical ports)
Tag typesNetwork variables
Number of tags per connection (=1 tag set)32 (31 tags if Controller status is included in the tag set.)
Maximum link data size per node46,208 bytes/Logical ports 92,416 bytes total
Maximum data size per connection1,444 bytes 2 To use a data size of 505 bytes or higher, the system must support a large forward open (an optional CIP specification). The CS, CJ, NJ, and NX-series Units support a large forward open, but before connecting to nodes of other companies, confirm that those devices also support it.
Number of registrable tag setsData concurrency is maintained within each connection.
32 per port (1 connection = 1 tag set) (total of 40 with two logical ports) 2 If more than 40 tag sets are registered in total, the Tag Data Link, Too Many Tag Sets Registered (840E0000 hex) event will occur.
Maximum size of 1 tag set1,444 bytes (Two bytes are used if Controller status is included in the tag set.)
Multi-cast packet filter 2 Because the built-in EtherNet/IP port is equipped with an IGMP client (version 2), unnecessary multicast packets can be filtered out by an Ethernet switch that supports IGMP Snooping.Supported.
CIP message service: Explicit messages 2 The built-in EtherNet/IP port uses the TCP/UDP port numbers shown in the following table. Do not set the same port number for more than one TCP/UDP service.Class 3 (number of connections)Connections: 16/Logical ports (total of 32 with two logical ports) (server only)
UCMM (unconnected)Maximum number of clients that can communicate at one time: 16 per port (total of 32 with two logical ports)Maximum number of servers that can communicate at one time: 16 per port (total of 32 with two logical ports)
TCP/UDP message serviceMaximum number of clients that can communicate at one time16 per port (total of 32 with two logical ports)
Maximum message sizeRequest: 492 bytes Response: 496 bytes
SNMPAgentSNMPv1, SNMPv2c
MIBMIB-II
EtherNet/IP conformance testConforms to CT14
Ethernet interface10BASE-T or 100BASE-TX Auto negotiation or fixed settings

Используемые номера портов TCP/UDP

Не устанавливайте один и тот же номер порта для нескольких служб TCP/UDP.

ServiceTypePort numberRemarks
Tag data linksUDP2222Fixed values
Used by systemUDP2223, 2224
TCP9610
CIP messagesTCP44818
FTP client (Data transfer port)TCP20
DNS clientTCP/UDP53
BOOTP clientUDP68
HTTP serverTCP80
Used by system, otherTCP/UDP9600You can change the port number in the Unit Settings on the Sysmac Studio.
FTP client (Control port)TCP21
TCP/UDP message serviceTCP/UDP64000
NTP clientUDP123
SNMP agentUDP161
SNMP trapUDP162

Блоки управления безопасностью

Unit nameSafety CPU Unit
ModelNX-SL5500
Maximum number of safety I/O points1024 points
Program capacity2048 KB
Number of safety master connections 2 This is the maximum number of Safety I/O connections that can be set to this Unit. The value is the total number of CIP Safety originator connections, CIP Safety target connections, and FSoE master connections.128
Number of CIP Safety originator connections128
Number of CIP Safety target connections4
Number of originators that can be connected with a multi-cast connection8
Number of FSoE master connections128
I/O refreshing methodFree-Run refreshing
External connection terminalsNone
Indicators
Hardware switch settings
Dimensions30 x 100 x 71 mm (W x H x D)
I/O power supply methodNot supplied.
Current capacity of I/O power supply terminalsNo I/O power supply terminals
NX Unit power consumption3.35 W max. 2 The cable length for the Units (Communication Control Unit and Power Supply Unit for NX Units) that supply power to the corresponding Unit must be up to 20 m.
Current consumption from I/O power supplyNo consumption
Weight130 g max.
Installation orientation and restrictionsInstallation orientation: Upright installation Restriction 2 Only NX102 CPU Units and Communication Control Units can be connected. NX1P2 CPU Units or Communications Coupler Units cannot be connected. : None.
Unit nameSafety Input Unit
ModelNX-SIH400
Number of safety input points4 points
Number of test output points2 points
Internal I/O commonPNP (sinking inputs)
Rated input voltage24 VDC (20.4 to 28.8 VDC)
OMRON special safety input devicesCan be connected.
Number of safety slave connections1
I/O refreshing methodFree-Run refreshing
External connection terminalsScrewless clamping terminal block (8 terminals)
Indicators
Safety input current4.5 mA TYP.
Safety input ON voltage11 VDC min.
Safety input OFF voltage/OFF current5 VDC max., 1 mA max.
Test output typeSourcing outputs (PNP)
Test output load current25 mA max.
Test output residual voltage1.2 V max. (Between IOV and all output terminals)
Test output leakage current0.1 mA max.
Dimensions12 x 100 x 71 mm (W x H x D)
Isolation methodPhotocoupler isolation
Insulation resistance20 MOhm min. between isolated circuits (at 100 VDC)
Dielectric strength510 VAC for 1 min between isolated circuits, leakage current: 5 mA max.
I/O power supply methodPower supplied from the NX bus
Current capacity of I/O power supply terminalsNo applicable terminals.
NX Unit power consumptionConnected to a CPU Unit or a Communication Control Unit 1.10 W max.Connected to a Communications Coupler Unit 0.70 W max.
Current consumption from I/O power supply20 mA max.
Weight70 g max.
Circuit layout
Terminal connection diagram
Installation orientation and restrictionsInstallation orientation: Connected to a CPU Unit or a Communication Control Unit 2 Only NX102 CPU Units and Communication Control Units can be connected. NX1P2 CPU Units cannot be connected. Possible in the upright installation orientation. Connected to a Communications Coupler Unit 6 possible orientations. Restrictions: Maximum ambient temperature is 50°C for any orientation other than upright installation.
Protective functionsOvervoltage protection circuit and short detection (test outputs)
Unit nameSafety Output UnitModelNX- SOH200NX- SOD400
Number of safety output points2 points4 points
Internal I/O commonPNP (sourcing outputs)
Maximum load current2.0 A/point 4.0 A/Unit at 40°C 2.5 A/Unit at 55°CThe maximum load current depends on the installation orientation and ambient temperature0.5 A/point and 2.0 A/Unit
Rated voltage24 VDC (20.4 to 28.8 VDC)
Number of safety slave connections1
I/O refreshing methodFree-Run refreshing
External connection terminalsScrewless clamping terminal block (8 terminals)
Indicators
Safety output ON residual voltage1.2 V max. (Between IOV and all output terminals)
Safety output OFF residual voltage2 V max. (Between IOG and all output terminals)
Safety output leakage current0.1 mA max.
Dimensions12 x 100 x 71 mm (W x H x D)
Isolation methodPhotocoupler isolation
Insulation resistance20 MOhm min. between isolated circuits (at 100 VDC)
Dielectric strength510 VAC for 1 min between isolated circuits, leakage current: 5 mA max.
I/O power supply methodPower supplied from the NX bus
Current capacity of I/O power supply terminalsIOG: 2 A max./terminalIOG (A3 and B3): 2 A max./terminal IOG (A7 and B7): 0.5 A max./terminal
NX Unit power consumptionConnected to a CPU Unit or a Communication Control Unit 1.05 W max. Connected to a Communications Coupler Unit 0.70 W max.Connected to a CPU Unit or a Communication Control Unit 1.10 W max. Connected to a Communications Coupler Unit 0.75 W max.
Current consumption from I/O power supply40 mA max.60 mA max.
Weight65 g max.
Circuit layout
Terminal connection diagram
Installation orientation and restrictionsInstallation orientation: Connected to a CPU Unit or a Communication Control Unit 2 Only NX102 CPU Units and Communication Control Units can be connected. NX1P2 CPU Units cannot be connected. Possible in the upright installation orientation. Connected to a Communications Coupler Unit 6 possible orientations. Restrictions: None
Protective functionsOvervoltage protection circuit and short detection (test outputs)

Модули ЦПУ безопасности NX-SL5500/SL5700

Unit nameSafety CPU Unit
ModelNX-SL5500
Maximum number of safety I/O points1024 points
Program capacity2048 KB
Number of safety master connections 2 This is the maximum number of Safety I/O connections that can be set to this Unit. The value is the total number of CIP Safety originator connections, CIP Safety target connections, and FSoE master connections.128
Number of CIP Safety originator connections128
Number of CIP Safety target connections4
Number of originators that can be connected with a multi-cast connection8
Number of FSoE master connections128
I/O refreshing methodFree-Run refreshing
External connection terminalsNone
Indicators
Hardware switch settings
Dimensions30 x 100 x 71 mm (W x H x D)
I/O power supply methodNot supplied.
Current capacity of I/O power supply terminalsNo I/O power supply terminals
NX Unit power consumption3.35 W max. 2 The cable length for the Units (Communication Control Unit and Power Supply Unit for NX Units) that supply power to the corresponding Unit must be up to 20 m.
Current consumption from I/O power supplyNo consumption
Weight130 g max.
Installation orientation and restrictionsInstallation orientation: Upright installation Restriction 2 Only NX102 CPU Units and Communication Control Units can be connected. NX1P2 CPU Units or Communications Coupler Units cannot be connected. : None.

Модули ввода безопасности NX-SIH400/SID800

Unit nameSafety Input Unit
ModelNX-SIH400
Number of safety input points4 points
Number of test output points2 points
Internal I/O commonPNP (sinking inputs)
Rated input voltage24 VDC (20.4 to 28.8 VDC)
OMRON special safety input devicesCan be connected.
Number of safety slave connections1
I/O refreshing methodFree-Run refreshing
External connection terminalsScrewless clamping terminal block (8 terminals)
Indicators
Safety input current4.5 mA TYP.
Safety input ON voltage11 VDC min.
Safety input OFF voltage/OFF current5 VDC max., 1 mA max.
Test output typeSourcing outputs (PNP)
Test output load current25 mA max.
Test output residual voltage1.2 V max. (Between IOV and all output terminals)
Test output leakage current0.1 mA max.
Dimensions12 x 100 x 71 mm (W x H x D)
Isolation methodPhotocoupler isolation
Insulation resistance20 MOhm min. between isolated circuits (at 100 VDC)
Dielectric strength510 VAC for 1 min between isolated circuits, leakage current: 5 mA max.
I/O power supply methodPower supplied from the NX bus
Current capacity of I/O power supply terminalsNo applicable terminals.
NX Unit power consumptionConnected to a CPU Unit or a Communication Control Unit 1.10 W max.Connected to a Communications Coupler Unit 0.70 W max.
Current consumption from I/O power supply20 mA max.
Weight70 g max.
Circuit layout
Terminal connection diagram
Installation orientation and restrictionsInstallation orientation: Connected to a CPU Unit or a Communication Control Unit 2 Only NX102 CPU Units and Communication Control Units can be connected. NX1P2 CPU Units cannot be connected. Possible in the upright installation orientation. Connected to a Communications Coupler Unit 6 possible orientations. Restrictions: Maximum ambient temperature is 50°C for any orientation other than upright installation.
Protective functionsOvervoltage protection circuit and short detection (test outputs)

Модули вывода безопасности NX-SOH200/SOD400

Unit nameSafety Output UnitModelNX- SOH200NX- SOD400
Number of safety output points2 points4 points
Internal I/O commonPNP (sourcing outputs)
Maximum load current2.0 A/point 4.0 A/Unit at 40°C 2.5 A/Unit at 55°CThe maximum load current depends on the installation orientation and ambient temperature0.5 A/point and 2.0 A/Unit
Rated voltage24 VDC (20.4 to 28.8 VDC)
Number of safety slave connections1
I/O refreshing methodFree-Run refreshing
External connection terminalsScrewless clamping terminal block (8 terminals)
Indicators
Safety output ON residual voltage1.2 V max. (Between IOV and all output terminals)
Safety output OFF residual voltage2 V max. (Between IOG and all output terminals)
Safety output leakage current0.1 mA max.
Dimensions12 x 100 x 71 mm (W x H x D)
Isolation methodPhotocoupler isolation
Insulation resistance20 MOhm min. between isolated circuits (at 100 VDC)
Dielectric strength510 VAC for 1 min between isolated circuits, leakage current: 5 mA max.
I/O power supply methodPower supplied from the NX bus
Current capacity of I/O power supply terminalsIOG: 2 A max./terminalIOG (A3 and B3): 2 A max./terminal IOG (A7 and B7): 0.5 A max./terminal
NX Unit power consumptionConnected to a CPU Unit or a Communication Control Unit 1.05 W max. Connected to a Communications Coupler Unit 0.70 W max.Connected to a CPU Unit or a Communication Control Unit 1.10 W max. Connected to a Communications Coupler Unit 0.75 W max.
Current consumption from I/O power supply40 mA max.60 mA max.
Weight65 g max.
Circuit layout
Terminal connection diagram
Installation orientation and restrictionsInstallation orientation: Connected to a CPU Unit or a Communication Control Unit 2 Only NX102 CPU Units and Communication Control Units can be connected. NX1P2 CPU Units cannot be connected. Possible in the upright installation orientation. Connected to a Communications Coupler Unit 6 possible orientations. Restrictions: None
Protective functionsOvervoltage protection circuit and short detection (test outputs)