| I/O characteristics | Rated input
voltage (Input voltage allowable range) | 24 VDC (20 to 30 VDC) | 24 VDC (20 to 28.8 VDC) | 24 VDC (20 to 30 VDC) | | | | | | |
| Allowable
input current 2 For power input terminals, use 35 A max. per pole. | 40 A | 15.2 A | 70 A | | | | | | | |
| Max. rated
output current (per output) | 10 A | 3.8 A | 10 A | | | | | | | |
| Internal
voltage drop 2 A voltage drop will occur in the S8V-CP. Consider
the voltage drop at the output. | 200 mV max. | 150 mV max. | 200 mV max. | | | | | | | |
| Output leakage
current | 10 mA max. | | | | | | | | | |
| Power consumption 2 When
selecting the power supply, be sure to include the internal power
consumption of the S8V-CP and not just the power consumption of
the load. | When all outputs are connected | 10 W max. (at 10 A) | 3.1 W max. (at 3.8 A) | 20 W max. (at 10 A) | | | | | | |
| When all output branches are tripped | 0.84 W typ. | 0.82 W typ. | 1.32 W typ. | | | | | | | |
| Start-up
time 2 Outputs start in order from +VO1 to +VO8. +VO1 starts after
the initialization time. Start-up delay time of each output is automatically
decided depending on the load. If the start-up delay time is over
5 s, the next output is forcibly started. | Initialization time | 250 ms typical | | | | | | | | |
| Start-up delay time | 50 ms to 5 s | | | | | | | | | |
| Functions 2 Refer
to Cat. No. T226-E1 for details. | Current
tripping function 2 Refer to Cat. No. T226-E1
for details. | Rated output current | 2 A, 3 A, 4 A, 6 A, 8 A, 10 A | 3.8 A | 2 A, 3 A, 4 A, 6 A, 8 A, 10 A | | | | | |
| Cutoff current | 2.5 A, 3.5 A, 4.5 A, 6.5 A, 8.5 A, 10.5 A | 3.8 A | 2.5 A, 3.5 A, 4.5 A, 6.5 A, 8.5 A, 10.5 A | | | | | | | |
| Over voltage
tripping function 2 Refer to Cat. No. T226-E1
for details. | No | Yes | No | | | | | | | |
| Push button
(ON/OFF/RESET) with indicator | Yes (LED colors: Red/Green/Yellow) | | | | | | | | | |
| Reset signal
input (RST) | Yes (High level: 15 to 30 VDC,
Low level: 0 to 5 VDC) | | | | | | | | | |
| Alarm signal
output (ALM1/ALM2) | Yes (MOS FET relay output 30 VDC
max., 50 mA max.) | | | | | | | | | |
| Insulation | Dielectric
strength | 1.0 kVAC for 1 min (between all
terminals and DIN rail mounting parts), current cutoff 20 mA | | | | | | | | |
| Insulation
resistance | 100 MOhm min. (between all terminals
and DIN rail mounting parts) at 500 VDC | | | | | | | | | |
| Environment | Ambient operating
temperature | -25 to 70°C (Derating is required
according to the temperature.) (with no condensation or icing) | | | | | | | | |
| Storage temperature | -40 to 85°C (with no condensation
or icing) | | | | | | | | | |
| Ambient operating
humidity | 5% to 96% (storage humidity: 5%
to 96%) | | | | | | | | | |
| Vibration
resistance | 10 to 55 Hz, maximum 5 G, 0.42
mm half amplitude for 2 h each in X, Y, and Z directions | | | | | | | | | |
| Shock resistance | 294 m/s2, 3 times each in +/-X,
+/-Y, +/-Z directions | | | | | | | | | |
| Reliability | MTBF 2 MTBF
is calculated according to JEITA RCR-9102. | 13,5000 hrs typ. | 60,000 hrs typ. | 13,5000 hrs typ. | | | | | | |
| Life expectancy 2 Refer
to Cat. No. T226-E1 for details. | 10 years min. | | | | | | | | | |
| Construction | Weight | 160 g max. | 170 g max. | 420 g max. | | | | | | |
| Cooling fan | No | | | | | | | | | |
| Degree of
protection | IP20 by EN/IEC 60529 | | | | | | | | | |
| Standards | EMI | Conforms to EN 61000-6-3 | | | | | | | | |
| EMS | Conforms to EN 61000-6-2 | | | | | | | | | |
| Safety standards | UL 508 (CSA22.2 No.14-10) Listing Pol2 UL 2367 Recognition (Max. 100W per output, per Class 2 limitations) Pol2 2 UL Class 2 output applies for the S8V-CP0424S model only. CE (EN 61000-6-2, EN 61000-6-3) | | | | | | | | | |